Security levels in IEC 62443 explained

In IEC 62443, a security level (SL) describes the kind of attacker a zone, conduit, system or component protects against. The scale runs from SL 1, protection against accidental violations, to SL 4, protection against attackers with extensive resources. Its three forms answer three questions: SL-T is the target, SL-C the capability and SL-A what has been achieved.

Zones page of the demo company with SL gaps per zone and foundational requirement and the network map with target security levels
Inhoud
  1. The four levels
  2. The three forms
  3. Seven foundational requirements instead of one number
  4. How to set the SL-T
  5. What one level higher means
  6. From gap to measure
  7. Example: a zone with an older controller
  8. Common mistakes
  9. Checklist
  10. Security levels in Complass
  11. Frequently asked questions
  12. Read more

Stand van:

This guide explains the four levels, the three forms and the seven foundational requirements. You will also see how to set a target and find gaps.

The four levels

The levels differ in whom you want to fend off. The examples in the last column are our own invented illustrations.

LevelProtection againstMeans and knowledgeExample
SL 1Accidental or coincidental violationsNo intentOperating error at the panel
SL 2Intentional attacksSimple means, few resources, general IT knowledge, low motivationAn offender uses a freely available tool against an open service
SL 3Intentional attacksSophisticated means, moderate resources, automation knowledge, moderate motivationA group with knowledge of control protocols
SL 4Intentional attacksAs SL 3, but extensive resources and high motivationVery well equipped attackers

The definitions are in Annex A of IEC 62443-3-2 and in IEC 62443-3-3. Use your licensed copy for the classification.

The three forms

  • SL-T (target). The target for a zone or conduit. It is a requirement, not an inventory, and comes from the risk assessment under IEC 62443-3-2.
  • SL-C (capability). What a system or component can deliver when properly configured. IEC 62443-3-3 covers systems, IEC 62443-4-2 covers components.
  • SL-A (achieved). What has actually been achieved in the plant, including compensating measures.

The difference matters in every project: an SL-C says what is possible. Only the SL-A shows whether the function is switched on and used.

Seven foundational requirements instead of one number

A security level does not apply across the board. IEC 62443-3-3 assigns requirements to seven foundational requirements (FR), and the target can differ for each FR. The questions in the last column are our own translation into practice.

FRFoundational requirementQuestion for the plant
FR 1Identification and authentication controlDo we know who is logging on?
FR 2Use controlIs this person allowed to do this?
FR 3System integrityDo programs and data stay unchanged?
FR 4Data confidentialityAre recipes and credentials protected?
FR 5Restricted data flowDoes only permitted traffic run between zones?
FR 6Timely response to eventsDo we detect and log incidents?
FR 7Resource availabilityDoes the plant keep running under load?

For a control zone, integrity and availability often come first, while confidentiality is frequently less critical. An SL-T can therefore be stated as a vector, for example {2, 2, 3, 1, 3, 2, 3} for FR 1 to FR 7.

Many asset owners start pragmatically with one value per zone and differentiate later.

How to set the SL-T

IEC 62443-3-2 does not prescribe a specific method for this. A proven sequence:

  1. Assess the zone and conduit. Determine threats, impact and likelihood without countermeasures.
  2. Place the attacker. Ask which kind of attacker the zone must withstand.
  3. Derive the level. Use the distance to the tolerable risk or the definitions of the levels, or raise the level step by step until the risk is tolerable.
  4. Check per FR. Decide whether one value is enough or individual foundational requirements differ.
  5. Justify and approve. Refer to the relevant scenarios. Approval rests with the asset owner.

Exposed areas such as the OT DMZ and remote maintenance conduits often need a higher SL-T than the zones behind them because of where they sit.

Network map of the demo company with the target security level per zone and the open gaps per foundational requirement
Network map with SL-T per zone and the gaps per foundational requirement (sample project).

What one level higher means

Requirements are added with each level. IEC 62443-3-3 contains 51 system requirements (SR) and 49 requirement enhancements (RE) that apply depending on the level. For the login of people, SR 1.1, it looks like this:

LevelWhat is required (in our own words)
SL 1All people are identified and authenticated
SL 2Each person is uniquely identified; group accounts are no longer enough
SL 3In addition, MFA for access over untrusted networks
SL 4MFA on all networks

Some system requirements apply only from SL 2 or SL 3. A higher target is therefore not automatically better, but above all more work.

From gap to measure

  1. Determine the SL-C. Use manufacturer information, certificates, security manuals and, for legacy systems, your own check.
  2. Compare. For each zone and FR, compare the SL-T with the state of the plant.
  3. Switch on what exists. You can close many gaps by activating existing functions, such as personal accounts on the panel.
  4. Compensate. If a system cannot meet a requirement, make up for it, for example with a tight firewall rule or a two-person rule for program changes.
  5. Plan the replacement. Record what the substitute measure stands in for and how long it should apply.

Example: a zone with an older controller

This example is invented. A zone in a filling plant has an SL-T of 2 in FR 1. The controller has no user management, so its SL-C in FR 1 stays below the target.

The operator panel supports personal accounts, but they have not been set up.

  • Panel: The accounts are activated. This needs no investment.
  • Controller: The zone boundary allows write access only from the engineering station, and program changes follow a two-person rule.
  • Plan: The measure stays in place until the planned replacement of the controller.

Common mistakes

  • Reading a security level as a product seal. The SL-C of a component says nothing about the SL-A of your plant.
  • Confusing the SL-T with the current state. The target comes from the risk, not from what exists.
  • One value without looking at the FRs. A single number for everything hides where the gap really is.
  • Choosing a level out of habit. Every level needs a reason.
  • Compensation as a permanent state. Substitute measures need a plan for their replacement.

Checklist

  • SL 1 to SL 4, SL-T, SL-C and SL-A are understood the same way across the team
  • Every zone and conduit has a justified SL-T
  • For important zones you have checked whether individual FRs differ
  • SL-C information has been requested from manufacturers
  • Legacy systems without information have been checked
  • Gaps per zone and FR are recorded in an action plan
  • Compensating measures have a reason and an end date

Security levels in Complass

A spreadsheet with seven columns per zone is quick to build but rarely stays up to date. With a booked IEC 62443 module, Complass keeps target, capability and status in one place:

  • SL-T from the assessment. In the zone assessment the portal proposes an SL-T from the risk class. You decide and apply the value to the zone.
  • Per foundational requirement. If you wish, you set the SL-T per FR 1 to FR 7. Without an own value, the zone value applies to all FRs.
  • SL-C on the asset. You maintain the values in the asset's master data.
  • SL-A and gap. As a starting value the portal takes the lowest SL-C value of the assets in operation. If a value is missing, SL-A stays open, and with a justification you can override SL-A in the zone.
  • Measure for the gap. From a gap you create a task in the action plan directly.
  • Catalogues for 3-3. You assess system requirements and enhancements with status and evidence, and you filter the enhancements by level. The implementation guide names steps, evidence and common findings.

The texts of the standard are not included, because standards are protected by copyright.

Frequently asked questions

Which security level do we need?

That follows from your risk assessment, not from an industry list. It depends on impact, threats and tolerable risk per zone.

Who sets the SL-T?

The asset owner. Integrators provide method and proposals, manufacturers the information on the SL-C.

Can a zone have a higher SL-A than its components?

Yes, that can happen. Compensating measures at the zone boundary or organisational rules can make up for capabilities that individual devices lack. Document for each measure which requirement it replaces.

What is the difference between a security level and a maturity level?

A security level describes technical protection. A maturity level assesses processes, such as the development process under IEC 62443-4-1. A process certificate of this kind says nothing on its own about the SL-C of a particular product.

In a demo we show you how SL-T, SL-C and SL-A come together in Complass.

Request a demo Try it for 14 days

Read more

Not legal advice. This guide gives a general overview and does not replace an assessment of the individual case. The wording of your licensed copy of the standard is authoritative.